Conversion of ATV32 to ATV320 Devices
Convert an ATV32 device configuration to an ATV320 device configuration by using the SoMove configuration software. As a prerequisite, the configuration file (*.psx) corresponding to the ATV32 device to convert is required.
|
Step |
Action |
|---|---|
|
1 |
Generating the ATV32 configuration file (*.psx). |
|
2 |
Converting the ATV32 device configuration to an ATV320 device configuration. |
|
3 |
Importing the converted ATV320 project into EcoStruxure Machine Expert. |
How to Generate the ATV32 Configuration File
|
Step |
Action |
Result |
|---|---|---|
|
1 |
Launch SoMove. |
The SoMove start page opens. |
|
2 |
Execute the command Tools > Edit Connection / Scan. |
– |
|
3 |
In the Edit Connection dialog box, select the connection settings that correspond to the ATV32 device you want to convert. For further information, refer to the SoMove online help. |
– |
|
4 |
Click Apply. |
The Edit Connection dialog box is closed. |
|
5 |
Execute the command Transfer > Load from Device from the SoMove start page. |
– |
|
6 |
Select a file to save the SoMove project. |
– |
|
7 |
Select the file type SoMove project files (*.psx). |
– |
|
8 |
Click Save. |
The upload process starts. |
How to Convert ATV32 to ATV320 Devices
|
Step |
Action |
Result |
|---|---|---|
|
1 |
Launch SoMove. |
The SoMove start page opens. |
|
2 |
Execute the command Tools > Device Conversion. |
The Device Conversion dialog box opens. |
|
3 |
Select the ATV32 configuration file (*.psx) that you want to convert, and click Open. |
The Device Conversion for ATV32 dialog box opens. |
|
4 |
Select ATV320 from the Select Target list and click Convert. |
The Select ATV320 dialog box opens. |
|
5 |
Select the option ATV320 Book or ATV320 Compact according to your requirements. |
The compatible Reference, Firmware Version, Supply Voltage, and Nominal Power parameters are displayed for the selected option. |
|
6 |
Click OK. |
The message Device conversion is successful is displayed. |
|
7 |
Click OK to close the message. |
The converted ATV320 project opens. |
How to Import the Converted ATV320 Project Into EcoStruxure Machine Expert
|
Step |
Action |
Result |
|---|---|---|
|
1 |
Launch SoMove. |
The SoMove start page opens. |
|
2 |
Execute the command Tools > Edit Connection / Scan. |
– |
|
3 |
In the Edit Connection dialog box, select the connection settings that correspond to the ATV320 device you want to update. For further information, refer to the SoMove online help. |
– |
|
4 |
Click Apply. |
The Edit Connection dialog box is closed. |
|
5 |
Execute the command Transfer > Store to Device. |
– |
|
6 |
Close SoMove. |
– |
|
7 |
Open your EcoStruxure Machine Expert project, and select Altivar 320 in the Devices tree. |
– |
|
8 |
Upload the device configuration for the ATV320 device. For more information, refer to the Device Type Manager (DTM) - User Guide. |
– |